3000VA/3000W Sine Wave UPS
3000VA/3000W Sine Wave UPS
- Price:
$1,925.99
- Availability:
- Mfr #: PR3000RTXL2UN
- UNSPSC #: 26111701
- Item #: 007270784
- Add to Shopping List
Need Help?
Contact Zones Online support at 800.408.9663
Miscellaneous
| Cables Included | Power cable - external - 10 ft ¦ USB cable - external ¦ Serial cable - external ¦ Emergency power off cable - external |
| Rack Mounting Kit | Included |
| Equipment Protection Value | 400000 US Dollars |
| Features | Audible alarm, emergency power off, overheat protection, Automatic Voltage Regulation (AVR), overcharge protection, overload protection, hot-swappable batteries, reset breaker, buck operation, booster technology, dataline protection, rotatable LCD panel, GreenPower UPS Bypass Technology, Fast Charge technology, Human Interface Device (HID) support, Battery Equalization Technology, internal current limiting, low battery alarm, overload alarm, overcharge alarm, overheat alarm |
| Compliant Standards | FCC Class A certified, VCCI, UL 1778, RoHS |
Networking
| Remote Management Interface | Ethernet 10/100, RS-232, USB |
| Remote Management Protocol | SNMP 1, SNMP 3, HTTP, HTTPS, SSH, CLI, SMTP, NTP |
Dimensions & Weight
| Width | 17.1 in |
| Depth | 19.7 in |
| Height | 3.4 in |
| Weight | 75.4 lbs |
Environmental Standards
| ENERGY STAR | Yes |
Dimensions & Weight (Shipping)
| Shipping Width | 22.1 in |
| Shipping Depth | 24.4 in |
| Shipping Height | 10.8 in |
| Shipping Weight | 89.51 lbs |
Software / System Requirements
| Software Included | PowerPanel Business Edition |
Sustainability Information
| ENERGY STAR | Yes |
Manufacturer Warranty
| Service & Support | Limited warranty - 3 years |
Battery
| Quantity | 4 |
| Technology | Lead acid |
| Voltage Provided | 12 V |
| Capacity | 9 Ah |
| Run Time (Up To) | 1.7 min at full load ¦ 7 min at half load |
| Recharge Time | 3 hours |
| Transfer Time | 4 ms |
| Switchover Time | 4 ms |
| Features | Sealed |
Environmental Parameters
| Min Operating Temperature | 32 °F |
| Max Operating Temperature | 104 °F |
| Humidity Range Operating | 0 - 95% (non-condensing) |
| Sound Emission | 57.5 dBA |
General
| Device Type | UPS - active Power Factor Correction (PFC) - rack-mountable / external |
| Height (Rack Units) | 2U |
| Color | Black |
Power Device
| UPS Technology | Line interactive |
| Input Voltage | AC 100-120 V |
| Input Voltage Range | AC 75 - 155 V |
| Input Voltage Range (Adjustable) | AC 70 - 155 V |
| Frequency Provided | 50/60 Hz ± 1% |
| Frequency Required | 47 - 63 Hz |
| Input Connectors | 1 x power NEMA L5-30P |
| Power Output Connectors Details | 8 x power NEMA 5-20R ¦ 1 x power NEMA L5-30R |
| Output Voltage | AC 100/110/120 V + 5% / - 5% - 50/60 Hz |
| Power Capacity | 3000 Watt / 3000 VA |
| Dataline Surge Protection | Network - RJ-45 - 1 input line / 1 output line |
| Output Waveform | Sinewave |
| Surge Suppression | Yes |
| Surge Energy Rating | 2430 Joules |
| Circuit Protection | Circuit breaker |
| Power Factor (PF) | 1.0 |
Expansion / Connectivity
| Interfaces | 1 x management (RS-232) - 9 pin D-Sub (DB-9) ¦ 1 x management (USB) - 4 pin USB Type B ¦ 1 x EPO (emergency power off) ¦ 1 x management (Ethernet) - RJ-45 ¦ 1 x management - RJ-45 ¦ 1 x dry contact |
| Expansion Slots | 1 (total) / 0 (free) x expansion slot |