- System overview: 900VA line-interactive UPS, large LCD volt meter and UPS function indicators, plus UPS and surge-only outlets
- Voltage compatibility: 120
- Frequency compatibility: 60
- Output volt amp capacity (VA): 900
- Output watt capacity (watts): 450
- Output nominal voltage: 120VAC
- Output voltage regulation: BATTERY MODE: PWM sine wave 115V +/-5%
- Output frequency regulation: LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
- Outlet quantity / type: 8 NEMA 5-15R output receptacles (4 with UPS and surge suppression / 4 with surge suppression only)
- Maximum input amps: 12a
- Input connection type: NEMA 5-15P
- Input cord length: 6 ft. / 1.8 m
- Recommended electrical service: 120V 15A
- Battery - Full load runtime: 3 minutes (900VA / 450 watts)
- Battery - Half load runtime: 11 minutes (450VA / 225 watts)
- DC system voltage: 12VDCTypical battery lifespan: 4-6 years (depending on usage)
- Battery recharge rate: 2-8 hours to 90%
- Voltage regulation description: Line interactive voltage regulation corrects brownouts as low as 89V back to usable values
- Direct pass through: Voltages of 105V and greater are passed through to connected equipment unchanged
- Brownout correction: Input voltages between 89 and 104 are boosted by 14%
- Front panel LEDs: Front panel LCD screen with blue backlight offers continuous input line voltage data, plus UPS status information on line power status, battery power status, battery charge level andvoltage regulation operation
- Alarms: Audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
- Switches: Includes 2 front panel switches - one main on/off power switch and one dual function "alarm cancel" / "self test" button
- AC surge suppression: 1920 joules
- AC suppression response time: Instantaneous
- EMI / RFI AC noise suppression: Yes
- Cold Start: Yes, inverter can be "cold started" to enable temporary AC output during a power failure
- Transfer time from line power to battery mode: 2-4 milliseconds
- Low voltage transfer to battery power: Switches to battery power as line voltage decreases to 89V or less, switches back to AC mode as line voltage increases to 94V or higher
- High voltage transfer to battery power: Switches to battery mode as line voltage increases to 139V or higher, switches back to AC mode as line voltage decreases to 135V or lower
- Certifications: UL1778 (TUV), cUL (TUV), NOM, FCC Class B
- Unit weight (lbs): 14.6
- Unit Dimensions (HWD/in): Tower format: 12 x 3.5 x 6.5 / Rackmount Shelf format: 3.5 x 12 x 6.5
- Form factors supported: Upright tower or Rackmount Shelf format (LCD panel is adjustable for either osition). Rackmount format requires optional shelf, available separately
- Cooling method: Convection
- Operating Temperature: +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
- Storage Temperature: +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
- Relative Humidity: 0 to 95%, non-condensing
- Product warranty: 2 year product warranty
- Connected equipment insurance (USA and Canada Only): $200,000 connected equipment insurance (USA and Canada only)
|
|